WIKA operating instructions RTD and TC, intrinsically safe designs (Ex i)
3345267.12 01/2014 GB/D
27
GB
7.3.2 Increasing the separation of the connection components and hot surfaces
The neck distance (N) is dened as the distance between the lower edge of the connection head
(or the housing) to the heat-emitting surface. The temperature to be expected at the lower edge
of the connection head or housing is, at most, 100 °C. The conditions for built-in transmitters or
displays must be observed. If required, the neck length must be increased accordingly.
For thermometers tted with a connection lead, the temperature at the interface with the
connecting cable is restricted. The maximum is 150 °C. To ensure that the permissible
temperature is not exceeded, the dimension X must be selected accordingly.
7. Information on mounting, operation in hazardous area (Europe)
3160670.06
Threaded connection
Thread
Thread
11355647.01
Thread
Thread
(NPT)