WIKA operating instructions bimetal thermometers for HVAC6
6. Indicator check
The check of the indicator should only be carried out in comparison with a more
accurate instrument or, if possible, with a calibrated instrument. The temperature
during the check must remain constant. Fluctuating temperatures may lead to
reading errors caused by the dierent response times of the probes.
For thermometers without protective sleeves, a minimum waiting time of
10 minutes, for temperature equalisation, should be observed, provided the
appropriate immersion length is adhered to.
Attention: Only gaseous pressure-free media are admissible!
For thermometers with protective sleeves, a minimum waiting time of at least
15 minutes, for temperature equalisation, should be observed, provided the
appropriate immersion length is adhered to.
Admissible working pressure at the pocket: max. 6 bar
7. Indicator correction
Any interference with or modication to the instrument will invalidate
the warranty!
The indicator correction built into the bottom of stem should only be operated
using a screwdriver, and only if the thermometer has been damaged due to
improper handling, severe shocks, during transport, etc.
When correcting an indication error using the adjustment mechanism, a
calibrated thermometer must be used for comparison. Subsequently, the
thermometer must be checked at several temperature points.
1) not for clip-on thermometer model A46.11 and edgewise panel design
model TF-01-058KF-BI