INSTRUCTION MANUAL
NI-222E
Rev. 1 12/02
Fig. 2 -
Electrical connections and adjustment screws
One contact instruments
Two contact instruments
Microswitch electrical circuit
State of the contacts at at-
mospheric pressure
1 - Microswitch set point calibration screws
3 - Terminal block
4 - Electrical connection identification plate
1 - Microswitch 2 set point calibration screws
2 - Microswitch 1 set point calibration screws
3 - Terminal block
4 - Electrical connection identification plate
Designation of the contacts:
C - common
NA - Normally open
NC - Normally closed
5 - SET POINT CALIBRATION
In order to proceed with the calibration and the periodical
functional verification of the instrument a suitable cali-
bration circuit (fig. 5) and an adequate pressure source
is required.
5.1 PRELIMINARY OPERATIONS
Weatherproof pressure switches (BWX)
Remove the blocking device fixed to the side of the in-
strument case and the adjustment screw access plate
(Fig. 3). Remove the cover by rotating it in an anticlock-
wise direction.
Fig. 3 - Weatherproof pressure switch blocking device -
a - Plumbing wire
b - Plumbing
c - Blocking nut
d - Blocking bracket
e - Adjustment screw access
plate
Explosionproof pressure switches (BAX) (Fig. 4)
CAUTION: do not open the cover of explosionproof
pressure switches (Series BAX) when energized, in
explosive atmospheres.
Loosen the locking headless screw situated on the
cover using a 1,5 hexagonal key then unscrew the cover.
Remove the internal blocking device inserted on the
closure plugs and slide out the plugs.
Fig. 4 -
Explosionproof pressure switch blocking device
5.2 CALIBRATION CIRCUIT AND OPERATIONS
Prepare the control circuit as indicated in Fig.5.
The warning lamps should be connected to contact 1 or
2 in the NO or NC position according to the required
contact action.
Connection of C and NO terminals
If the circuit is open at the working pressure, the
switch closes the circuit as the pressure increases
when the desired value is reached.
If the circuit is closed at the working pressure, the
switch opens the circuit as the pressure decreases
when the desired value is reached.
Connection of C and NC terminals
If the circuit is closed at the working pressure, the
switch opens the circuit as the pressure increases
when the desired value is reached.