Conformity specifications
For instruments with ATEX approval the following conformity specifications,
which differ slightly from the specifications indicated in the data sheet, are
applicable:
Power supply: 14 … 30 DC V
Short circuit rating: Imax ≤ 100 mA
Power: Umax ≤ 1000 mW
Internal capacitance: Ci ≤ 12 nF
Internal inductance: negligible
Safety instructions for installation
Observe the installation and safety instructions included in
the operating instructions
≤Install the instruments in accordance with the instructions of
the manufacturer and the applicable standards and regula-
tions
≤Seal the cable entries using approved cable glands so that
they are leak-tight
≤Only use cable glands which possess an ATEX Ex e appro
-
val and have an ingress protection of at least IP 65.
Fix the connection cable securely
≤If intrinsically safe equipment is installed in hazardous areas,
it must only be operated as part of a certified intrinsically
safe circuit.
Transmitter supply isolators
When using ATEX instruments, an Ex transmitter supply isolator is an absolute
requirement.
We recommend Model KFD2-STC4-Ex1 with a power supply of 20 ... 35 DC V,
installation on standard rail, our order number 2341268
11297264 05/2009 GB/D/F/E
WIKA Operating Instructions intelliGAUGE family
16
8. Instruments with ATEX approval