8 WIKA operating instructions model TR21
GB
3. Specications
Output signal Pt100
Temperature range Measuring range -50 ... +150 °C, -50 ... +250 °C
Measuring element Pt100 (measuring current: 0.1 ... 1.0 mA) standard measuring resistor
Pt100 (measuring current: 0.1 ... 1.0 mA) face-sensitive measuring
resistor
1)
Connection method 3-wire
4-wire
Sensor tolerance value
2)
per DIN EN 60751
Class B
Class A
Class AA
Output signal 4 ... 20 mA
Temperature range Measuring range -50 ... +150 °C, -50 ... +250 °C
3)
Measuring element Pt100 (measuring current: 0.5 mA) standard measuring resistor
Pt100 (measuring current: 0.5 mA) face-sensitive measuring resis-
tor
1)
Connection method 3-wire
Sensor tolerance value
2) 4)
per DIN EN 60751
Class B
Class A
Class AA
Measuring span minimum 20 K, maximum 300 K
Basic conguration
Measuring range -50 ... +150 °C, -50 ... +250 °C depending on the
selected temperature range, other measuring ranges are adjustable
Analogue output 4 ... 20 mA, 2-wire
Measuring deviation
per DIN EN 60770, 23 °C ±5 K
0.2 % (Transmitter)
4)
Linearisation linear to temperature per DIN EN 60751
Linearisation error ±0.1 %
5)
Switch-on delay, electrical < 10 ms
Signalling of sensor burnout congurable: NAMUR downscale < 3.6 mA (typically 3 mA)
NAMUR upscale > 21.0 mA (typically 23 mA)
Sensor short-circuit
not congurable, generally NAMUR downscale < 3.6 mA (typically
3 mA)
Load R
A
R
A
≤ (U
B
- 10 V) / 0.023 A with R
A
in Ω and U
B
in V
Eect of load ± 0.05 % / 100 Ω
Power supply DC 10 ... 35 V
Max. permissible residual ripple 10 % at 24 V / maximum 300 Ω Load
Power supply input protected against reverse polarity
3. Specications
Readings in % refer to the measuring span
For a correct determination of the overall measuring error, both sensor and transmitter measuring deviations have to
be considered.
1)
The small design of the face-sensitive measuring resistors leads to reduced heat dissipation with short insertion lengths.
Available for temperature range -50…+150 °C in Classes A and B.
Face-sensitive measuring resistors are generally used for thermowell insertion lengths smaller than 11 mm.
2)
For detailed specications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com
3)
The temperature transmitter should therefore be protected from temperatures over 85 °C
4)
For measuring spans smaller than 50 K additional 0.1 K
5)
± 0.2 % for measuring ranges with a lower limit less than 0 °C