11 Diagnostics and Service
The following error messages can appear on devices with displays
(see chapter 5.1.3):
12 Disposal
If a failure cannot be repaired, the transmitter must be switched off.The op-
erator then must make sure that it is only switched on again after the failure
has been repaired.
Repairs should only be carried out by the manufacturer. All other repairs or
modifications are unauthorized.
Error Code Error Error Correction Measures
E00 ROM-error Return device to manufacturer
E01 Power supply error Check power supply
E03
E
2
PROM communications error
Disconnect and reconnect power
supply
E04 Sensor’s temperature range was
exceeded
Return sensor’s temperature to
specified limits
E06 Sensor recognition Disconnect and reconnect power
supply
E07 General communications error
between the sensor and the con-
trol interface unit
Check the connection between
the sensor and the control inter-
face unit
E08
Error E
2
PROM
send in transmitter for service
Sen Error 0 Sensor recognition Check the connection between
the sensor and the control inter-
face unit
When storing or disposing the pressure transmitter, take precautions with
regard to remaining media. Remaining media in the pressure port may
be hazardous or toxic!
Dispose of instrument components and packaging materials in
accordance with the respective waste treatment and disposal regulations
of the region or country to which the instrument was supplied.
Attention
Important