8
Parameter
Rel.
Index
Description Type Store
Size
byte
RO /
R/W
Min. Max. Default
FAULT_STATE
28
Active E D Condition set by loss of communication to an out
-
put block, failure promoted to an output block or a physical
contact. When Fault State condition is set, Then output func
-
tion blocks will perform their FSAFE actions.
Un-
signed
8
N 1 RO 1
SET_FSTATE
29
Allows the fault state condition to be manually initiated by
selecting Set.
Un-
signed
8
D 1 R/W 1
CLR_FSTATE
30
Writing a Clear to this parameter will clear the device fault state
if the field condition, if any, has cleared.
Un-
signed
8
D 1 R/W 1
MAX_NOTIFY
31 Maximum number of unconfirmed notify messages possible.
Un-
signed
8
SRC 1 RO 8
LIM_NOTIFY
32
Maximum number of unconfirmed alert notify messages
allowed.
Un-
signed
8
SRC 1 R/W 8
CONFIRM_TIME
33 Ms The minimum time between retries of alert reports.
Un-
signed
32
SRC 4 R/W 640000
WRITE_LOCK
34
If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated.
Un-
signed
8
SRC 1 R/W 1
UPDATE_EVT
35 This alert is generated by any change to the static data DS-73 D 14 RO
0,0,0,
0,0,9,0
BLOCK_ALM
36
The block alarm is used for all configuration, hardware, con
-
nection failure or system problems in the block. The cause
of the alert is entered in the sub code field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert report
-
ing task, another block alert may be reported without clearing
the Active status, if the sub code
has changed.
DS-72
D 13 R/W
0,0,0,
0,0,0,
8,0,0
ALARM_SUM
37
The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function
block.
DS-74 Mix 8 R/W 0,0,0,0
ACK_OPTION
38
0: Auto ACK Disable
1: Auto ACK Enable
Selection of whether alarms associated with the block will be
automatically acknowledged.
BIT_
STRING
SRC 2 R/W 0
WRITE_PRI
39 Priority of the alarm generated by clearing the write lock.
Un-
signed
8
SRC 1 R/W 0
WRITE_ALM
40 This alert is generated if the write lock parameter is cleared. DS-72 D 13 R/W
0,0,0,
0,0,0,
10,0,0
ITK_VER_NR
41
ITK Version Number
This parameter informs which ITK version is the device (for cer-
tified devices only).
Un-
signed
16
SRC 2 RO 4