14016442.01 06/2011 GB/D
10 WIKA operating instructions model TR30 per ATEX
GB
3. Specications
3.1 Output signal Pt100, model TR30-P
Measuring element and measuring insert
The Pt100 measuring element is located in the thermometer's probe tip.
Output signal Pt100, model TR30-P
Temperature range Measuring range without neck tube -50 ... +150 °C, with neck tube -50 ... +250 °C
Measuring element Pt100 (measuring current: 0.1 ... 1.0 mA)
Connection method 2-wire
3-wire
4-wire
Sensor tolerance value
1)
per DIN EN 60751
Class B
Class A
Electrical connection Angular DIN connector Form A, M12 x 1 circular connector, 4-pin
Explosion protection
(option)
Intrinsically safe to Ex-i (ATEX) gas/dust, per Directive 94/9/EC
Marking: II 1G Ex ia IIC T* or II 2D Ex iaD 21 T*
Readings in % refer to the measuring span
For a correct determination of the overall measuring error, both sensor and transmitter measuring deviations have to
be considered.
1)
For detailed specications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com.
3.2 Output signal 4 ... 20 mA, model TR30-W
Measuring element and measuring insert
The Pt100 measuring element is located in the thermometer's probe tip.
The 4 ... 20 mA transmitter is mounted and potted within the tubular body of the
thermometer.
Output signal 4 ... 20 mA, model TR30-W
Temperature range Measuring range without neck tube -50 ... +150 °C,
with neck tube -50 ... +250 °C
2)
Measuring element Pt100 (measuring current: 0.5 mA)
Sensor tolerance value
1)
per DIN EN 60751
Class B
Measuring span minimum 20 K, maximum 300 K
Basic conguration Measuring range 0 ... 150 °C, other measuring ranges are adjustable
Analogue output 4 ... 20 mA, 2-wire
Measuring error
per DIN EN 60770, 23 °C ±5 K
0.2 % (Transmitter)
3)
Linearisation linear with temperature per DIN EN 60751
Linearisation error ±0.1 %
4)
Switch-on delay, electrical < 10 ms
Signalling of sensor burnout congurable: NAMUR downscale < 3.6 mA (typically 3 mA)
NAMUR upscale > 21.0 mA (typically 23 mA)
Sensor short-circuit
not congurable, generally NAMUR downscale < 3.6 mA (typ. 3 mA)
Load R
A
R
A
≤ (U
B
- 9 V) / 0.023 A with R
A
in Ω and U
B
in V
Eect of load ± 0.05 % / 100 Ω
3. Specications