12 WIKA operating instructions pressure transmitter, model R-1
14026284.01 11/2012 GB/D/F/E
GB
3. Specications
3.4 Reference conditions (per IEC 61298-1)
Temperature
15 ... 25 °C
Atmospheric pressure
860 ... 1,060 mbar
Humidity
45 ... 75 % relative
Power supply
DC 24 V
Nominal position
Calibrated in vertical mounting position with pressure connection facing downwards.
3.5 Accuracy data
Accuracy at reference conditions
≤ 2 % of span
Including non-linearity, hysteresis, zero oset and end value deviation (corresponds to measured error
per IEC 61298-2).
Temperature error at -25 ... +85 °C
Mean temperature coecient of zero point: typical ≤ 0.5% of span/10 K
Mean temperature coecient of span: ≤ 0.3 % of span/10 K
Zobrazit stránku 11