11WIKA operating instructions pressure transmitter model A-10
11218720.10 01/2012 GB/D/F/E
GB
3. Specications
3.2 Output signal
Signal type Value Load in Ω
Current (2-wire) 4 ... 20 mA ≤ (power supply - 8 V) / 0.02 A
Voltage (3-wire) DC 0 ... 10 V
DC 0 ... 5 V
DC 1 ... 5 V
DC 0.5 ... 4.5 V
> maximum output signal / 1 mA
Ratiometric (3-wire) DC 0.5 ... 4.5 V > 4.5k
Other output signals available on request.
3.3 Voltage supply
Power supply
Output signal Power supply
Standard Option
4 ... 20 mA DC 8 ... 30 V DC 8 ... 35 V
1)
DC 0 ... 10 V DC 14 ... 30 V DC 14 ... 35 V
DC 0 ... 5 V DC 8 ... 30 V DC 8 ... 35 V
DC 1 ... 5 V DC 8 ... 30 V DC 8 ... 35 V
DC 0,5 ... 4,5 V DC 8 ... 30 V DC 8 ... 35 V
DC 0,5 ... 4,5 V ratiometrisch DC 5 V ± 10 % -
1) Not possible with non-linearity 0.25 % BFSL.
The power supply for the pressure transmitter must be made via an energy-limited electrical circuit in accordance with section 9.3 of UL/
EN/IEC 61010-1, or an LPS to UL/EN/IEC 60950-1, or class 2 in accordance with UL1310/UL1585 (NEC or CEC). The power supply must
be suitable for operation above 2,000 m should the pressure transmitter be used at this altitude.
Total current consumption
Signal type Total current consumption
Current (2-wire) Signal current, max. 25 mA
Voltage (3-wire) 8 mA
Ratiometric (3-wire) 8 mA