Strany 1 - Profibus PA

Differential pressure transmitter DPT10 - metal mea-suring diaphragmProfibus PADocument ID:37245

Strany 2 - Contents

Density measurement=∆phg+–hFig. 5: Density measurement with DPT10, h = defined mounting distance, Δp =differential pressure, ρ = density of the medium,

Strany 3

The configuration of the measuring cells differs depending on themeasuring range:123451p2pFig. 7: Metallic measuring cell 10 mbar and 30 mbar - p1and p2

Strany 4 - 1 About this document

a PDM environment, an EDD (Electronic Device Description) is alsorequired to enable the full range of sensor functions (also available asa download).

Strany 5 - 2 For your safety

l Not exposed to corrosive medial Protected against solar radiationl Avoiding mechanical shock and vibrationl Storage and transport temperature see ch

Strany 6 - 2.6 CE conformity

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Strany 7 - 3 Product description

You find general recommendations for wiring of effective pressurelines in DIN 19210 "Effective pressure lines for flow systems" or thecorrespond

Strany 8 - 3.2 Principle of operation

4.3 Measurement setup flowà Mount DPT10 above the measurement loop so that condensatecan drain off in the process cable.+–1243Fig. 10: Measurement setup

Strany 9

+ – 1 2 3 3 5 5 6 6 7 4Fig. 11: Measurement setup, flow measurement in vapours1 Condensate vessels2 Orifice or impact pressure probe3 Blocking valves4 D

Strany 10 - 37245-EN-100120

+ – 1 2 2 35 5 6 4 4 Fig. 12: Measurement setup, flow measurement in liquids1 Orifice or impact pressure probe2 Blocking valves3 DPT104 Precipitator5

Strany 11

à For measurements in products with solid content such as e.g. dirtyliquids, the installation of separators and drain valves isrecommended to enable c

Strany 12 - 3.3 Operation

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Strany 13

à Mount DPT10 below the lower measurement connection so thatthe effective pressure lines are always filled with liquidà Connect minus side always above

Strany 14 - 4 Mounting

+ – max. min. + –1 234Fig. 16: Measurement setup, level measurement in closed vessel1 Blocking valve2 Precipitator3 Drain valve4 DPT10à Mount DPT10 be

Strany 15

à Connect minus side always above the max. levelà The condensate vessel ensures a constant pressure on the minussideà For measurements in products wit

Strany 16 - 4.3 Measurement setup flow

+ – min. max. 12345+ –Fig. 19: Measurement setup in closed vessel with superimposed steam1 Condensate vessel2 Blocking valve3 Precipitator4 Drain valv

Strany 17

à Mount DPT10 below the lower isolating diaphragmà The ambient temperature should be the same for both capillariesInformation:An interface measurement

Strany 18 - 4.4 Measurement setup level

4.6 Measurement setup differential pressureà Mount DPT10 above the measurement loop so that condensatecan drain off in the process cable.+12343Fig. 22:

Strany 19

+ – 1 2 4 5 6 4 5 2 3 Fig. 23: Measurement setup, flow measurement in liquids1 E.g. filter2 Blocking valves3 DPT104 Precipitator5 Drain valves6 3-fold v

Strany 20

4.7 Mounting arrangement and connection valveblockThe following illustration shows the elements for a tube mounting andan example for a mounting arran

Strany 21

The following illustration shows the connection of a 5-fold valve block.A:A51 2435 7 89 62184 67 93Fig. 26: Connection of a 5-fold valve block1 Proces

Strany 22

8 Oval flange adapter9 Fixing screws4.8 External housing1 Mark the holes according to the following drilling template2 Depending on the mounting surfac

Strany 23

6.6 Menu schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . .556.7 Saving the parameter adjustment data . . . . . . . . . . . .587 Setup

Strany 24

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Strany 25

Take note of the corresponding installation regulations for Exapplications. In particular, make sure that no potential equalisationcurrents flow over t

Strany 26

The electrical connection is finished.Fig. 28: Connection steps 6 and 7Proceed as follows:1 Loosen the four screws on the housing base with an Allen ke

Strany 27

2 Remove the housing socket from the mounting plate321Fig. 29: Components of the external housing1 Screw2 Wall mounting plate3 Cable gland3 Loop the c

Strany 28

5.3 Single chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.I²CDisplay1 2 5 6 7 83412Fig. 30: Electronics

Strany 29 - 4.9 Mounting control

5.4 Double chamber housingThe following illustration apply to non-Ex as well as Ex ia versions. TheExd version is described in the next subchapter.132

Strany 30 - 5 Connecting to power supply

312Display1 2I²CFig. 33: Connection compartment double chamber housing1 Plug connector for service2 Ground terminal for connection of the cable screen

Strany 31 - 5.2 Connection procedure

5.5 Double chamber housing Ex d132Display1 2 5 6 7 8I²CFig. 35: Electronics compartment, double chamber housing1 Plug connector for service2 Internal

Strany 32

11 2Fig. 37: Wiring plan with double chamber housing Ex d1 Voltage supply/Signal output5.6 Version IP 66/IP 68, 1 bar+-12Fig. 38: Wire assignment, con

Strany 33

5.7 External housing with version IP 685 6 7 81 2DisplayI²C45123Fig. 39: Electronics and connection compartment1 Plug connector for service2 Spring-lo

Strany 34 - 5.3 Single chamber housing

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Strany 35 - 5.4 Double chamber housing

1 2 3 434125Fig. 40: Connection of the sensor in the housing socket1 Brown2 Blue3 Yellow4 White5 ShieldingI2CDisplay11 2 56 7 8Fig. 41: Wiring plan ex

Strany 36

l Internal check of the electronicsl Indication of the instrument type, the firmware as well as thesensor TAG s (sensor designation)l Status byte goes

Strany 37

6 Adjustment with the indicating andadjustment module6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay, adju

Strany 38

Fig. 42: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous me

Strany 39

6.3 Adjustment system1.1231Fig. 43: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mo

Strany 40 - 5.8 Switch on phase

6.4 Parameter descriptionDPT10 has general adjustment parameters which are also used forother measuring principles as well as instrument-specific adjus

Strany 41

In this menu item you select the adjustment unit as well as the unit f orthe temperature indication in the display.To select the adjustment unit (in t

Strany 42 - 6.1 Short description

Unit of measurementDensity0001000kg/dm³6 Enter the requested density value with [->] and [+], confirm with[OK] and move to position correction with

Strany 43

If a known value should be taken over as position correction which isnot the current value, then you have to select the function "Edit" ande

Strany 44 - 6.3 Adjustment system

Proceed as follows:1 Edit the % value in the menu item "Min. adjustment" with [OK].Min. adjustment0.00 %=0.0000 bar0.0000 bar2 Set the reque

Strany 45 - 6.4 Parameter description

2 For your safety2.1 Authorised personnelMount and set up the pressure transmitter only if you know theapplicable national regulations and have the ap

Strany 46

2 Set the requested bar value with [+] and [->].3 Confirm with [+] and move to max. adjustment with [->].For an adjustment with flow, simply enter

Strany 47

Linearisation curvelinearEnter the requested parameter via the appropriate keys, save yoursettings and jump to the next menu item with the [->] key

Strany 48

Part sum counter0 % = +0000m3/s=100 % = +0000m3/s=6 Edit with [OK] and set the requested values with [+] and [->].7 Confirm with [OK] and jump back

Strany 49

Menu item Reset valueBasic settings Unit of measurement barTemperature unit °CZero/Min. adjustment Measuring range beginSpan/Max. adjustment Measuring

Strany 50 - 0.0000 bar

6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment different

Strany 51

6.6 Menu schematicBasic adjustment flow1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Sensor address1261.1ApplicationFlow▼1.1UnitUnit of measurement

Strany 52

Display2Basic adjustment▶DisplayDiagnosticsServiceInfo2.1Displayed valueDifferential pressure▼2.1Displayed valuePA-Out2.2Display unitVolume▼l▼2.3Scalin

Strany 53

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Additional PA valueSecondary Value 14.2Out-Scale-UnitVolumel4.3PA-Out-Scale100.00 lin %= 0.0

Strany 54 - 6.5 Menu schematic

6.7 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Strany 55 - 6.6 Menu schematic

7 Setup with PDM7.1 Parameter adjustment with PDMFor WIKA sensors, instrument descriptions are also available as EDDsfor the adjustment program PDM. T

Strany 56 - Diagnostics

2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the

Strany 57

8 Set up8.1 Select the modeThe following modes can be adjusted on DPT10:l Flow measurementl Level measurementl Differential pressure measurement8.2 Flo

Strany 58

AB+1567+–243IIIIIIIIIFig. 45: Preferred installation for liquidsI DPT10II 3-fold valve blockIII Precipitator1.5 Drain valves2.4 Inlet valves3 Breather

Strany 59 - 7 Setup with PDM

4 Carry out a position correction if the following conditions apply. Ifthe conditions are not fulfilled, then carry out the positioncorrection after st

Strany 60 - 8 Set up

Fig. 46: Preferred installation for open vesselsI DPT10II Precipitator1 Drain valve6.7 Vent valves on DPT10A Blocking valveProceed as follows:1 Fill t

Strany 61

+AB6732415+–IIIIIIIIIFig. 47: Preferred installation for closed vesselsI DPT10II 3-fold valve blockIII Precipitator1, 5 Drain valves2, 4 Inlet valves6

Strany 62 - 8.3 Level measurement

+AB6732415+–IIIIIIIIIIVFig. 48: Preferred installation for closed vessels with steam overlayI DPT10II 3-fold valve blockIII PrecipitatorIV Condensate

Strany 63

Now:Valve 3, 6 and 7 are closedValves 2, 4, A and B are open.Then carry out adjustment, see chapter "Set parameters".8.4 Density and interfa

Strany 64

AB+1567+–243IIIIIIIIIFig. 50: Preferred installation for liquidsI DPT10II 3-fold valve blockIII Precipitator1.5 Drain valves2.4 Inlet valves3 Breather

Strany 65

Open valve 4: Connect minus sideNow:Valves 1, 3, 5, 6 and 7 are closed6)Valves 2 and 4 openValves A and B open (if available)Then carry out adjustment

Strany 66

9 Maintenance and fault rectification9.1 MaintainWhen the instrument is used properly, no special maintenance isrequired in normal operation.In some ap

Strany 67

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l DPT10 differential pressure transmitterl Depending on the version ventilation

Strany 68

? Measured value on the indicating and adjustment module does notcorrespond to the value in the PLCl The menu item "Display - Display value"

Strany 69 - 9.2 Rectify malfunctions

9.3 Instrument repairYou can download a return form (24 KB) in the Internet from ourhomepagewww.wika.com under the item "Service".If a repai

Strany 70

10 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temp

Strany 71 - 9.3 Instrument repair

11 Supplement11.1 Technical dataGeneral dataPressure type Differential pressureMeasuring principle PiezoresistiveCommunication interface I²C busMateria

Strany 72 - 10 Dismounting

Max. torque screws mounting strap 30 NmMax. torque screws socket external housing 5 Nm (3.688 lbf ft)Weight approx. 4.2 … 4 .5 kg (9.26 … 9.92 lbs), d

Strany 73 - 11 Supplement

Additional output parameter - temperatureProcessing is made via output signal HART multidrop, Profibus PA and Foundation FieldbusRange -50 … +150 °C (-

Strany 74

Influence of the installation position basicversion≤ 4 mbar9)10)A position-dependent zero-point shift can be corrected (see also chapter "General

Strany 75

Measuring range Thermal changes of the zerosignal and the output span relat-ing to the adjusted span-10 … +60 °C (+14 … +140 °F) 10 mbar, 30 mbar ±(0.

Strany 76

Measuring cell 10 mbar 30 mbar 100 mbar 500 mbarInfluence of the sys-tem pressure to thezero point±0.28 % of URL/7 bar±0.70 % of URL/70 bar±0.42 % of U

Strany 77

Heating time - all versionsWarm-up time ≤ 10 sLong-term stability (similar to DIN 16086, DINV 19259-1 and IEC 60770-1)Applies to digital interfaces (H

Strany 78

l Hardware and software versionl Article numbers, documentation3.2 Principle of operationDPT10 is a differential pressure transmitter for measurement o

Strany 79

Seal material Temperature limitsFKM, cleaned for oxygen application -10 … +60 °C (-4 … +140 °F)PTFE, cleaned for oxygen application -20 … +60 °C (-4 …

Strany 80

- Double chamber housing l 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopper M20 x 1.5; plug M12 x 1 forthe external indicating and adju

Strany 81

- Min. bending radius at 25 °C/77 °F 25 mm (0.985 in)- Diameter approx. 8 mm (0.315 in)- Colour BlueCable entry/plug22)- External housing l 2 x cable

Strany 82

Electrical protective measuresProtection rating- Housing, standard IP 66/IP 6723)- Aluminium and stainless housing (optio-nally available)IP 68 (1 bar

Strany 83

11.2 Information on Profibus PAInstrument master fileThe instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.These

Strany 84

PROFIBUS PA-outputTargetModeFailuremodeAlarmsScalingSource forscalingtiDampingSensorcharacteristicsPA-Out°CTBFB 2Fig. 53: DPT10: Block diagram with te

Strany 85

l Additional Cyclic ValueByte-No.1 2 3 4 5 6 7 8 9 10 11 12 13 1415FormatValueIEEE-754-FlieskommazahlPA -OUT(FB1)StatusStatus(FB1)IEEE-754-Flieskommaz

Strany 86

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded.The status "Measured value OK" is

Strany 87

StatuscodeDescription according to Pro-fibus standardPossible cause0 x 89 good (non-cascade) - active ad-visory alarm - low limitedLo-Alarm0 x 8a good

Strany 88

11.3 DimensionsPlastic housing1~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4.41")M20x1,5/½ NPT2~ 87 mm (3.43")ø 84 mm(3.31")120 mm (4

Strany 89 - 11.3 Dimensions

Level measurement123h =∆pρ g++––h+ –Fig. 3: Level measurement with DPT10. Δp = differential pressure, ρ = density ofthe medium, g = acceleration of gra

Strany 90

Aluminium housing in protection rating IP 66/IP 68 (1 bar)116mm (4 9/16")~ 150mm (5 29/32")ø 84mm (3 5/16")M20x1,5M20x1,51M20x1,5/½ NPT

Strany 91

Oval flange, connection ¼-18 NPT or RC ¼41,3 mm (1.63")85 mm(3.35")134,5 mm (5.3")41,3 mm (1.63")72 mm(2.84")128 mm (5.04"

Strany 92

Version Connection Fastening Material EquipmentU RC 1/4 7/16-20 UNF AISI 316L incl. 2 vent valves(316L)1 1/4-18 NPTIEC 61518PN 160: M10, PN420: M12Ste

Strany 93

Version Connection Fastening Material EquipmentV RC 1/4 7/16-20 UNF AISI 316L incl. 4 closing screws(AISI 316L) and 2ventilation valvesOval flange, pre

Strany 94

INDEXAAdjustment- Unit 46- with differential pressure 48- with ow 49-50- with level 49Application area- Density measurement 10- Differential pressure

Strany 95

Differential pressure transmitter DPT10 - metal measuring diaphragm • Profibus PA 95Index37245-EN-100120

Strany 96

WIKA Alexander Wiegand SE & Co. KGAlexander-Wiegand-Straße 3063911 Klingenberg/GermanyPhone +49 9372 132295Fax +49 9372 132706e-mail: support-tron