Linearisation curve
linear
Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
In some application, small ow quantities should not be detected. With
the creeping quantity suppression, the ow value can be suppressed
up to a certain % value. The default value is 5 % of the max. ow value,
corresponding to 0.25 % of the max. dierential pressure value. The
limit value is 50 %. This function depends on the selected linearization
function and is only available with root extracted characteristics.
The square root/bidirectional square root characteristics is very steep
at the zero point. This means that small changes in the measured
dierential pressure cause big changes in the output signal. The leak
volume suppression stabilises the signal output.
The DPT10 has two internal totalizers. For both you can adjust volume
or mass as count function as well as separately the unit.
Proceed as follows:
1 Select, for exa mple, menu item "Part su m counter".
Part sum counter
0.0000 10
00
gal
Modify settings?
2 Activate the function "Modify settings?" with [OK].
Part sum counter
Eective pressure transmitter
Unit
3 Conrm with [OK] "Eective pressure transmitter".
Part sum counter
Mass ow
Volume ow
Without unit
4 Select the requested variable with [->] and conrm with [OK].
5 Select calibration unit of the eective pressure transmitter with [-
>], for example m
3
/s and conrm w ith [OK].
Leak ow volume sup-
pression with ow
Total amounts counter
and subtotalizer with
ow
Dierential pressure transmitter DPT10 - metal measuring diaphragm Probus PA 51
6 Adjustment with the indicating and adjustment module
37245-EN-100120