Wika DPT-10 Uživatelský manuál Strana 25

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 96
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 24
4.6 Measurement setup dierential pressure
à Mount DPT10 above the measurement loop so that condensate
can drain o in the process cable.
+
1
2
3
4
3
Fig. 22: Measurement setup, dierential pressure measurement in gases and
vapours
1 DPT10
2 3-fold valve block
3 Blocking valves
4 E.g. lter
à Mount DPT10 below the measurement loop so that the eective
pressure lines are always lled with liquid and gas bubbles can
bubble up to the process line
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
In gases and vapours
In liquids
Dierential pressure transmitter DPT10 - metal measuring diaphragm Probus PA 25
4 Mounting
37245-EN-100120
Zobrazit stránku 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 95 96

Komentáře k této Příručce

Žádné komentáře