WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
9.Congurationviadisplayandoperatingunit
9.1.2 Conguringlevelmeasurement
1. Open the operating menu with [↵].
Select “Basic setting” and conrm with [↵].
2. Select Application” and conrm with [↵].
3. Select “Level” and conrm with [↵].
4. Select “Unit” and conrm with [↵].
5. Select length unit and conrm with [↵].
Length unit is set.
6. Select “Density” and conrm with [↵].
7. Select “Density unit” and conrm with [↵].
8. Select density unit and conrm with [↵].
Density unit is set.
9. Select “Density value” and conrm with [↵].
10. Set digit using [▲] [▼] and conrm with [↵]. The
cursor moves to the next digit. Repeat for each digit.
Density value is set.
11. Go back two menu levels using [ESC].
Select “Mode” and conrm with [↵].
12. Select “Level” and conrm with [↵].
Mode is set.
13. Perform a mounting correction.
See chapter 9.5 “Mounting correction (oset)”.