WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
11. Detail setup
11.3 Settingthealarmsignal
Alarmsignaldownscale(3.5mA)
In the event of a failure in the process transmitter, the output signal changes itself to
3.5 mA.
Alarm signal upscale (21.5 mA)
In the event of a failure in the process transmitter, the output signal changes itself to
21.5 mA.
1. Open the operating menu with [↵].
Select “Detail setup" and conrm with [↵].
2. Select “Current out” and conrm with [↵].
3. Select Alarm signal” and conrm with [↵].
4. Select alarm signal and conrm with [↵].
3.5 mA = alarm signal downscale
21.5 mA = alarm signal upscale
Alarm signal is set.
11.4 Settingthesignallimits
The signal limits dene the current range within which the output signal can be. Above
or below the signal limits are the preset limits for the output signal.
Setting range: 3.8 ... 20.5 mA or 4.0 ... 20.0 mA
(NAMUR recommendation for process instruments is 3.8 ... 20.5 mA)
1. Open the operating menu with [↵].
Select “Detail setup" and conrm with [↵].
2. Select “Current out” and conrm with [↵].
3. Select “Limits” and conrm with [↵].
3. Select signal limits and conrm with [↵].
Signal limits are set.